ÖÐÎÄ°æ | English  
News
Company Everts >
Industry news >
Technical support >
Common problem >
 
 
News The current position£ºhome page > Industry news    

Shenzhen generator cooling equipment

Author£ºgdlhwt Time£º2014-08-27  

The generator can generate a lot of heat during operation, the efficiency of heat when the temperature rises to a certain extent will affect the power generation unit. We must take measures to keep Shenzhen generator cooling. The air flow path is correct air from the tail section through the radiator of the engine, and then by a dismountable exhaust pipe discharged outdoors. If there is no exhaust pipe exhaust hot gas outdoor, fans will be the hot air pumping scattered around, the hot air will reduce the short circuit back to the radiator, cooling effect.

Air entrance and exit are big enough, enough to allow air to freely, about the vent is at least 1.5 times the radiator core area. Air entrance should have shutters evil example weather protection, the plate can be fixed, but it is best to be mobile in cold weather, without using this machine, the window leaf can be closed to keep warm, and contribute to the generator and load which makes the room. Turbine automatic starting, automatic switch shutter its also necessary, it should be set on the machine to start immediately to open. Don't rely on the radiator with heat exchange cooling system, production of Shenzhen turbine heat still needs to be discharged outside.

 

 

 

 
Address£º65 zhikang road lisonglang gongming street ,Guangming District, Shenzhen City, Guangdong Province, China
Telephone£º+86-0755-27272798 Email£ºtn075527272798@163.com
United Watt Technique Co.,Ltd will provide the best service for you!
Copyright(C) United Watt Technology Co., Ltd. ÔÁICP±¸18027529ºÅ